APC Smart-UPS On-Line,6000 Watts /6000 VA,Input 230V /Output 230V, Interface Port Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB, Extended runtime model, Rack Height 4 U
Output
Output Power Capacity 6000 Watts / 6000 VA
Max
Configurable Power 6000 Watts / 6000 VA
Nominal Output
Voltage 230V
Output Voltage
Distortion Less than 3%
Output
Frequency (sync to mains) 50/60Hz +/- 3 Hz
Other Output
Voltages 220, 240
Crest Factor 3
: 1
Topology Double
Conversion Online
Waveform Type
Sine wave
Output
Connections
(1) Hard Wire
3-wire (H N + G)
(6) IEC 320 C13
IEC 320 C13
(4) IEC 320 C19
IEC 320 C19
(2) IEC Jumpers
Bypass Internal
Bypass (Automatic and Manual)
Input
Nominal Input Voltage 230V
Input Frequency
40 - 70 Hz (auto sensing)
Input
Connections
Hard Wire 3
wire (1PH+N+G)
Input voltage
range for main operations 160 - 275V
Input voltage
adjustable range for mains operation 100 - 275V
Other Input
Voltages 220, 240
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended
electrolyte : leakproof
Typical
recharge time 1.50 hour(s)
Replacement
Battery APCRBC140
RBC™ Quantity 1
Extended Run
Options APC Smart-UPS SRT 6000VA RM 230V
Runtime Graph
Curve Part
Number(s)
A SRT6KRMXLI
B SRT6KRMXLI
+ (1)SRT192RMBP
C SRT6KRMXLI
+ (2)SRT192RMBP
D SRT6KRMXLI
+ (3)SRT192RMBP
E SRT6KRMXLI
+ (4)SRT192RMBP
Hover over the
line on the graph above to view the runtime at any desired load
Curve fit to
measured runtime data. All measurements taken with new, fully charged
batteries, at typical environmental conditions, with no electrical input and
balanced resistive load (PF = 1.0) output.
View Enlarged
Graph View Runtime Chart
Energy
Use/Efficiency
Load Efficiency
25% 92.7%
50% 94.4%
75% 94.6%
100% 94.4%
Hover over the
line on the graph above to view the efficiency at any desired load
Curve fit of
data measured in accordance with the ENERGY STAR Program Requirements Product
Specification for Uninterruptible Power Supplies (UPSs) - Eligibility Criteria
Version 1.0. All measurements taken in normal mode(s), at typical environmental
conditions, with 230V/50Hz electrical input and balanced resistive load (PF =
1.0) output.
Communications & Management
Interface
Port(s) Contact Closure, RJ-45 10/100 Base-T, RJ-45 Serial, Smart-Slot, USB
Available
SmartSlot™ Interface Quantity 1
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms prioritized by severity
Emergency Power
Off (EPO) Yes
Surge
Protection and Filtering
Surge energy
rating 480 Joules
Physical
Maximum Height 174.00 mm
Maximum Width
432.00 mm
Maximum Depth
719.00 mm
Rack Height 4U
Net Weight
60.00 KG
Shipping Weight
67.00 KG
Shipping Height
370.00 mm
Shipping Width
610.00 mm
Shipping Depth
960.00 mm
Color Black
Units per
Pallet 6.00
Environmental
Operating Environment 0 - 40 °C
Operating
Relative Humidity 0 - 95% no%
Operating
Elevation 0-3000 meters
Storage
Temperature -15 - 45 °C
Storage
Relative Humidity 0 - 95% no%
Storage
Elevation 0-15000 meters
Audible noise
at 1 meter from surface of unit 55.00 dBA
Online Thermal
Dissipation 1300.00 BTU/hr
Protection
Class IP 2